Honeywell RTH5160D1003 Non-Programmable Thermostat Installation Manual

The Honeywell RTH5160D1003 is a non-programmable thermostat for conventional forced air, heat pump, radiant heat and cool-only systems. It mounts on the UWP Mounting System and runs on two AA alkaline batteries. The Quick Installation Guide, document 33-00200EF-01, carries 19 numbered steps, from turning the power off at the breaker to the System Setup numbers.


Download / Preview Manual

32 pages: English on pages 1 to 16, then the French version on pages 17 to 32.


Honeywell RTH5160D1003 Product Specifications

Specification Details
Brand Honeywell
Model RTH5160 Series (D1003 is the catalog number; the PDF prints only the series name)
Product Type Non-programmable thermostat
Screen Home screen; Menu, Next (+) and Edit (-) buttons; alert icon and alert number shown on screen
System Types Conventional forced air, heat pump, radiant heat (boiler), cool only
Stages Up to 2 cool stages or 1 compressor stage; up to 2 heat stages, 1 aux/E stage
Power Two AA alkaline batteries. C does not power the thermostat display or operations; batteries are always required.
Terminals Not Supported L/A, S, U
Mounting UWP Mounting System, three #8 1-1/2 in. screws, 7/32 in. drill bit
Document 33-00200EF-01, 32 pages, PDF
Warranty 1 year limited, excluding battery

Frequently asked questions

Q: Does the RTH5160 need a C wire?

A: Not for power. C does not power the thermostat display or operations; batteries are always required. When the old labels do not match the new terminals, a single C or C1 wire goes to the C terminal; if there are two, wrap each separately with electrical tape and do not connect them.

Q: What batteries does it take?

A: Two AA alkaline batteries. The low battery icon appears about two months before the batteries are depleted, and the batteries should be replaced once a year even if the icon does not appear.

Q: Why is the display blank?

A: Make sure fresh AA alkaline batteries are properly installed, as shown on page 7.

Q: Why can’t I change the system setting to Cool?

A: Check System Setup Option 220 and make sure it is set to 1 or 2, as described on page 9.

Q: What does it mean when Heat On or Cool On flashes?

A: Compressor protection feature is engaged. Wait 5 minutes for the system to restart safely, without damage to the compressor.