Honeywell Digital Thermostat T6811DP08 Instruction Manual

Honeywell Digital Thermostat T6811DP08 Instruction Manual

The Honeywell Digital Thermostat T6811DP08 User Manual helps technicians install, wire, configure and troubleshoot this non-programmable thermostat for two-pipe fan coil systems. This guide covers the installation document, terminal designations, operating controls, installer settings, test procedures and common faults. It also explains the electrical safety precautions required before working on this 110 VAC thermostat.

Quick Facts and Specifications

The T6811DP08 is a digital fan coil thermostat designed for manual heating and cooling selection, ventilation and three-speed fan control. It is relevant to building maintenance teams working with fan coil units in hotels, apartments, offices and similar facilities.

Specification

T6811DP08 Details

Model

Honeywell T6811DP08

Supply voltage

110 (+20%, −10%) VAC

Supply frequency

50/60 Hz

System application

Two-pipe fan coil

Control modes

Heat, Cool and Vent

System selection

Manual heating/cooling changeover

Fan control

Three speeds: Low, Medium and High

Temperature setting range

10–32°C

Temperature control accuracy

±1°C at 21°C

Electrical load rating

4(2) A

Protection rating

IP20

Operating temperature

−18 to 49°C

Installation

Wall-mounted

Mounting boxes

86 × 86 mm or 2 × 4 inch junction box

Programming

Non-programmable; no seven-day schedule

Important: The T6811DP08 is a line voltage thermostat, not a conventional 24 VAC low-voltage thermostat. Do not assume that wiring instructions for other Honeywell models apply to this unit.

Where to Download the Official Manual PDF

The principal installation document for this thermostat family is identified as 62-0325ES-01. It covers the T6811DP08 and T6812DP08 models.

Installation Instructions: 62-0325ES-01

This document is the primary reference for installation and servicing. It includes display indicators, terminal designations, wiring diagrams for two-wire and three-wire valve actuators, wall mounting, Installer Setup, Installer Test, normal operation and troubleshooting.

View the T6811DP08/T6812DP08 Installation Instructions PDF. This is an archived copy of a Honeywell-branded document, rather than a verified current manufacturer-hosted download.

Understanding the Display

Indicator

Meaning

Temperature

Displays room temperature or the value selected by the display configuration.

Setpoint

Identifies the selected temperature setting.

Current Mode

Shows the active mode: Heat, Cool or Vent.

Heating or Cooling Demand

Indicates that the thermostat is calling for heating or cooling.

Keypad Lock

Indicates that keypad lockout is active.

Setup

Indicates Installer Setup mode.

Test

Indicates Installer Test mode.

Setup/Test Number

Identifies the configuration item or test function displayed.

The display's appearance can vary according to the active mode and installer configuration.

Button and Switch Functions

  • UP: In normal Heat or Cool operation, increases the selected temperature setpoint. It also changes values in Installer Setup and Installer Test modes.
  • DOWN: Decreases the temperature setpoint or changes the value of the selected configuration item.
  • MODE: Cycles through Heat, Cool and Vent.
  • POWER switch: Turns the thermostat on or off.
  • FAN switch: Selects Low, Medium or High fan speed.

In Vent mode, the fan operates without a heating or cooling demand from the thermostat. If a button appears unresponsive, check whether the thermostat is switched off, keypad lockout is active or Vent mode has been selected.

Terminal Designations and Wiring Diagram

Correct terminal identification is essential when installing or replacing a Honeywell T6811DP08.

Terminal

Function

Application

L

Line voltage power

Incoming live supply

Ch/Cc

Heating close / Cooling close

Valve actuator control

W/Y

Heating open / Cooling open

Valve actuator control

N

Neutral supply connection

Electrical supply common

Gl

Low-speed fan

Fan motor low-speed input

Gm

Medium-speed fan

Fan motor medium-speed input

Gh

High-speed fan

Fan motor high-speed input

Wiring terminology: The original document's extracted terminal table describes N as a line-voltage ground connection. Do not interpret this as permission to connect neutral and protective earth together. Confirm the actual supply and protective-earth requirements against applicable electrical regulations and verified manufacturer documentation before wiring.

Two-Wire Valve Actuator

The installation document includes a typical ON/OFF control arrangement for a two-pipe heating/cooling system with a two-wire valve actuator. The actuator wiring arrangement depends on its electrical design. Follow the manufacturer's diagram to identify the correct actuator connections and the terminals used for opening and closing. Do not infer a complete actuator circuit from terminal names alone.

Three-Wire Valve Actuator

The manual also illustrates a typical arrangement for a three-wire valve actuator. A three-wire actuator may use different connections for its control functions than a two-wire ON/OFF actuator. The exact connections depend on the actuator design and must match the wiring diagram supplied for that device.

Before connecting the valve, establish:

  • Whether the actuator is designed for the available supply voltage.
  • Which conductors provide the required control functions.
  • Which thermostat terminals the verified diagram specifies.
  • Whether the existing system is configured for heating or cooling.

Do not interchange two-wire and three-wire actuator wiring arrangements without confirming compatibility.

DANGER: 110 VAC LINE VOLTAGE — ELECTRIC SHOCK HAZARD

The T6811DP08 operates from a 110 VAC nominal supply. Contact with live conductors can cause serious injury or death.

  • Disconnect the electrical supply before installation, wiring, inspection or maintenance.
  • Verify that the circuit is de-energised using an appropriate test instrument.
  • Do not treat this thermostat as a 24 VAC low-voltage device.
  • Have installation and electrical troubleshooting performed by a qualified electrician or HVAC technician.
  • Restore power only after all connections, covers and mounting screws have been checked.

Wiring Diagram Reference

Consult the wiring diagrams in document 62-0325ES-01 for the illustrated two-wire and three-wire actuator arrangements. Never use a generic fan coil wiring diagram as a substitute for the correct diagram for the installed valve, fan motor and supply arrangement.

Installation Steps

Step 1: Mount the Back Cover

Isolate the electrical supply. Pull the existing conductors through the wiring opening and position the back cover over the wall junction box. The thermostat is intended for installation on an 86 × 86 mm or 2 × 4 inch junction box, subject to confirmation of the actual mounting arrangement.

Step 2: Secure the Back Cover

Insert the mounting screws and tighten them securely. Check that the back cover sits correctly against the mounting surface without pinching or damaging conductors.

Step 3: Connect the Wires

Loosen the relevant screw terminals. Insert each conductor into its designated terminal and tighten the terminal screw. Verify every connection against the correct wiring diagram before proceeding.

Step 4: Fit the Thermostat Body

Align the top of the thermostat with the back cover. Push the body down into position as shown in the installation instructions. Check that the housing is properly seated.

Step 5: Tighten the Locking Screw

Insert the locking screw into the hole at the bottom of the thermostat and tighten it. Before restoring power, check the wiring, enclosure, terminal tightness and mechanical fit.

After installation, confirm normal display operation, fan-speed selection, mode selection and heating or cooling response.

Installer Setup Menu Walkthrough

Installer Setup changes how the thermostat operates. Incorrect settings can prevent the device from controlling the intended HVAC system correctly.

Entering Installer Setup

  1. Ensure the thermostat is powered and accessible.
  2. Press and hold UP and MODE simultaneously for three seconds.
  3. Confirm that the display indicates Installer Setup.
  4. Press UP or DOWN to change the selected setting.
  5. Press MODE to advance to the next function.
  6. Press and hold UP and MODE simultaneously for three seconds to exit and save the settings.

Record the original settings before making changes, particularly in occupied buildings where the thermostat is part of a larger maintenance system.

Installer Setup Number Reference Table

The following reference is based on the settings listed in document 62-0325ES-01. Verify the values against a legible original copy before relying on them for commissioning.

Number

Name

Available Values

Default

1

System Type

0: Heat only; 1: Cool only; 2: Two-pipe, manual heating/cooling

2

9

Temperature Scale

°F or °C; verify displayed option coding against the original table

°C

13

CPH Value for Heat

1–12

4

14

CPH Value for Cool

1–6

3

18

Display Temperature Adjustment

−2, −1.5, −1, −0.5, 0, +0.5, +1, +1.5, +2°C, with corresponding Fahrenheit values

0°C

19

Temperature Display Mode

0: Room temperature; 1: Setpoint

0

20

Heating Range Stops

10–32°C; 50–90°F

32°C / 90°F

21

Cooling Range Stops

10–32°C; 50–90°F

10°C / 50°F

22

Keypad Lockout

0: All keys available; 1: All keys locked out

0

  • System Type 1 selects a cooling-only configuration; System Type 0 selects heating-only.
  • System Type 2 is the listed default for two-pipe manual heating/cooling operation.
  • CPH means cycles per hour. Change these parameters only when the application and manufacturer guidance justify doing so.
  • Setting 18 adjusts the displayed temperature offset. It should not be used to conceal an actual HVAC control or sensor fault.
  • Settings 20 and 21 establish heating and cooling setpoint limits.
  • Setting 22 controls keypad lockout.

The original table's temperature-scale option coding should be checked against a legible copy of the relevant document before reproducing it as an exact menu-value sequence: [VERIFY].

Installer Test Mode

Installer Test mode helps a qualified technician check heating and cooling outputs independently of normal user operation.

Entering Installer Test

  1. Press and hold UP and DOWN simultaneously for three seconds.
  2. Confirm that Installer Test mode is displayed.
  3. Use UP or DOWN to change the selected test value.
  4. Press MODE to advance to the next test function.
  5. Exit by pressing and holding UP and MODE simultaneously for three seconds.

Number

Function

Available Values

10

Heating Test

0: Heat Off; 1: Heat On

30

Cooling Test

0: Cool Off; 1: Cool On

70

Software Information

Press UP to view items 71–73

71

Software Version

Major version

72

Software Version

Minor version

73

Identification Code

Software identification value

Items 71–73 display information associated with the installed thermostat. Read the actual values from the device; do not assume them from another unit.

During output tests, verify the system's response and follow the site's electrical safety procedures. Do not force a valve or fan output if doing so could damage connected equipment.

Daily Operation

Switching the Thermostat On or Off

Use the physical POWER switch to turn the thermostat on or off. After switching it on, check the display and confirm that the selected mode matches the intended system operation.

Selecting Fan Speed

Move the FAN switch to the required setting:

  • Low: Low fan speed.
  • Medium: Medium fan speed.
  • High: High fan speed.

The selected speed determines the fan output used during operation.

Selecting Heat, Cool or Vent

Press MODE to select the required operating mode.

  • Heat: The thermostat can call for heating when the room temperature and setpoint require it.
  • Cool: The thermostat can call for cooling when the room temperature and setpoint require it.
  • Vent: Only the fan operates; the thermostat does not call for heating or cooling in this mode.

In a two-pipe fan coil system, heating or cooling availability also depends on the water supplied to the coil and the building's seasonal changeover arrangement.

Adjusting the Temperature

In Heat or Cool mode, press UP or DOWN to select the desired temperature. The available setting range is 10–32°C, subject to configured heating or cooling limits.

This is a non-programmable thermostat. It does not support a seven-day schedule or programmable daily heating and cooling periods.

Troubleshooting

Use the following checks before replacing the thermostat. For line-voltage testing or suspected wiring faults, consult a qualified technician.

Symptom

Possible Cause

Recommended Action

Heating does not start

Incorrect mode or setpoint

Select Heat and set the target temperature above room temperature.

Cooling does not start

Incorrect mode or setpoint

Select Cool and set the target temperature below room temperature.

Heating or cooling demand is absent

No active call for heating or cooling

Check the displayed mode, room temperature and setpoint.

Output is indicated, but the room does not change temperature

Valve, water supply, fan coil or building-system fault

Check the valve actuator, fan operation and availability of heating or chilled water.

Fan does not operate

Incorrect fan setting, supply issue or fan motor fault

Check the FAN switch and have the electrical supply and motor inspected safely.

Fan runs, but heating or cooling is ineffective

Valve or coil issue, unsuitable water temperature or restricted airflow

Inspect the fan coil and associated HVAC system.

MODE button does not respond

Thermostat is off or keypad is locked

Check the POWER switch and keypad lockout setting.

UP or DOWN does not respond

Keypad lockout, Vent mode or thermostat switched off

Check the operating mode, POWER switch and Setting 22.

Temperature display seems inaccurate

Display offset or sensor-related issue

Check Setting 18 and verify room temperature independently.

Thermostat appears completely dead

Supply interruption, wiring fault or device failure

Have a qualified technician verify the supply and connections.

For heating or cooling calls, the installation document recommends allowing approximately five minutes for the system to respond after checking the mode and setpoint.

Do not assume that a displayed heating or cooling demand proves the valve, fan motor or wider building system is functioning correctly.

Maintenance, Keypad Lock and Temperature Display Adjustment

Routine Maintenance

Keep the thermostat housing clean and free from dust. Use a soft, dry cloth and avoid spraying liquid directly onto the device. Do not open the housing or clean the terminal block while the circuit is energised.

During planned maintenance, check the mounting, enclosure, visible wiring condition and operation of the display and controls.

Keypad Lockout

Keypad lockout is controlled by Installer Setup Setting 22.

  • 0: All keys available.
  • 1: All keys locked out.

If the buttons appear to be disabled, have an authorised technician check Setting 22. Restore the intended setting after maintenance.

Temperature Display Adjustment

Setting 18 adjusts the displayed temperature by an offset from −2°C to +2°C. Setting 19 selects whether the display shows room temperature or the setpoint.

Before changing either setting, compare the display with a suitable independent thermometer and record the original configuration. If the temperature difference persists, investigate the installation and wider control system rather than relying solely on an offset adjustment.

Alternatives and Replacements

Honeywell T6812DP08

The T6812DP08 is the 220 VAC counterpart identified in the T6811DP08/T6812DP08 installation document. It may be relevant where the building's supply voltage differs from the T6811DP08 requirement.

However, the models must not be treated as interchangeable without checking the actual supply, load requirements, wiring arrangement and full model identification.

Upgrading to a Programmable Thermostat

A programmable thermostat may be suitable where building operators need scheduled temperature changes, occupancy-based operation or integration with a broader building-control strategy.

The replacement must be explicitly compatible with the installation's electrical supply, fan coil configuration, valve actuator and fan-speed outputs. Do not replace the T6811DP08 with a generic 24 VAC thermostat without confirming compatibility. A device designed for low-voltage control may not be suitable for a 110 VAC installation.

For hotels, hospitals and commercial buildings, have the proposed replacement approved by the responsible HVAC engineer or controls contractor.

Leave a Reply